THERMOSTAT HVAC CONTROLLER 24VAC BAS N2 OPEN COMMUNICATION
Part No: TEC2156H-2
Manufacturer: JOHNSON CONTROLS
Stock No: SQ22705
SKU No: 276089

Image is for illustrative purposes only. Please refer to product description.
Stock may not be available at all store locations. Inventory quantites can change without notice.
• Power & Communication: Operates on 19 to 30 VAC (24 VAC nominal) power and communicates via a Building Automation System (BAS) N2 Bus.
• Outputs: Features two proportional 0–10 VDC analog outputs (AO1/AO2), three fan relay outputs (High, Medium, Low), and an auxiliary triac output (BO5).
• Inputs & Sensors: Includes two binary inputs, one universal input, one remote sensor connection, and an internal 10k ohm Type II NTC thermistor for temperature sensing.
• Ranges & Accuracy: Display range spans -40°F to 122°F [-40°C to 50°C] with temperature accuracy of ±0.9°F. Heating setpoints range from 40°F to 90°F and cooling setpoints from 54°F to 100°F.
• Physical & Compliance: Measures 125 × 86 × 29 mm and weighs 0.34 kg. It is UL listed and FCC Part 15 Class A compliant.
Terminal Pinout Overview
• Terminals 1–3: Fan-H (High), Fan-M (Medium), and Fan-L (Low).
• Terminals 4–5: 24 V~ Hot and 24 V~ Com power supply connections.
• Terminals 6–7: BO5 Aux (Auxiliary Triac Output).
• Terminals 8 & 11: Unused/blank on proportional 5 models.
• Terminals 9 & 10: AO2 (0–10 VDC Heating) and AO1 (0–10 VDC Cooling).
• Terminals 12–16 & N2 Block: BI1, Remote Sensor (RS), Sensor Common (Scom), BI2, UI3, alongside the N2 Bus (+, –, REF) block.